Flux communicates with physical devices using ModbusTCP protocol for real-time monitoring and control.

PowerPack BESS

Overview

PowerPack battery energy storage systems provide grid-scale energy storage with advanced control capabilities.

Specifications

  • Capacity: 100-500 kWh
  • Power: 50-250 kW
  • Communication: ModbusTCP
  • Response Time: <1 second

Modbus Registers

RegisterAddressTypeDescription
Target Power2008RWPower setpoint (kW)
SOE2026ROState of Energy (%)
Status2000ROSystem status
Available Blocks2028ROInverter capacity
Command Source2010RWControl mode ID

Control Sequence

// Read current state
soe := client.ReadRegister(2026)
status := client.ReadRegister(2000)

// Calculate and send command
if status == READY {
target := calculateTarget(soe)
client.WriteRegister(2008, target)
}

Acuvim II Meters

Overview

High-accuracy power meters for monitoring site electrical parameters.

Measurements

  • Voltage (L-L, L-N)
  • Current (per phase)
  • Power (active, reactive, apparent)
  • Energy (import/export)
  • Power factor
  • Frequency

Modbus Configuration

meter:
type: acuvim2
modbus:
address: 1
baud: 9600
parity: none
data_bits: 8
stop_bits: 1

Register Map

ParameterStart AddressData TypeScale
Voltage L1-N0x0000Float321
Current L10x0010Float321
Power Total0x0040Float321000
Energy Import0x0100Float321

Communication Protocol

ModbusTCP Frame

Transaction ID: 2 bytes
Protocol ID: 2 bytes (0x0000)
Length: 2 bytes
Unit ID: 1 byte
Function Code: 1 byte
Data: Variable

Read Holding Registers (0x03)

// Read 10 registers starting at 2000
request := []byte{
0x00, 0x01, // Transaction ID
0x00, 0x00, // Protocol ID
0x00, 0x06, // Length
0x01, // Unit ID
0x03, // Function Code
0x07, 0xD0, // Start Address (2000)
0x00, 0x0A, // Quantity (10)
}

Write Single Register (0x06)

// Write value to register 2008
request := []byte{
0x00, 0x01, // Transaction ID
0x00, 0x00, // Protocol ID
0x00, 0x06, // Length
0x01, // Unit ID
0x06, // Function Code
0x07, 0xD8, // Register Address (2008)
0x00, 0x64, // Value (100)
}

Error Handling

Common Modbus Exceptions

CodeNameDescription
0x01Illegal FunctionFunction code not supported
0x02Illegal AddressRegister address invalid
0x03Illegal ValueValue outside valid range
0x04Device FailureDevice unable to process

Retry Logic

func readWithRetry(addr uint16, retries int) (uint16, error) {
for i := 0; i < retries; i++ {
val, err := client.ReadRegister(addr)
if err == nil {
return val, nil
}
time.Sleep(time.Second * time.Duration(i+1))
}
return 0, fmt.Errorf("max retries exceeded")
}

Configuration Examples

BESS Configuration

devices:
bess:
- id: "uuid-here"
name: "Site-BESS-01"
type: "powerpack"
modbus:
host: "192.168.1.100"
port: 502
address: 1
timeout: 5s
retry_count: 3

Meter Configuration

devices:
meters:
- id: "uuid-here"
name: "Grid-Meter"
type: "acuvim2"
modbus:
host: "192.168.1.101"
port: 502
address: 2
timeout: 5s

Testing Tools

modpoll

# Read BESS SOE
modpoll -m tcp -a 1 -r 2026 -c 1 192.168.1.100

# Write target power
modpoll -m tcp -a 1 -r 2008 -c 1 192.168.1.100 50

mbscan

# Scan for devices
mbscan -p 502 192.168.1.0/24

Next Steps