Flux communicates with physical devices using ModbusTCP protocol for real-time monitoring and control.

PowerPack BESS​

Overview​

PowerPack battery energy storage systems provide grid-scale energy storage with advanced control capabilities.

Specifications​

  • Capacity: 100-500 kWh
  • Power: 50-250 kW
  • Communication: ModbusTCP
  • Response Time: <1 second

Modbus Registers​

RegisterAddressTypeDescription
Target Power2008RWPower setpoint (kW)
SOE2026ROState of Energy (%)
Status2000ROSystem status
Available Blocks2028ROInverter capacity
Command Source2010RWControl mode ID

Control Sequence​

// Read current state
soe := client.ReadRegister(2026)
status := client.ReadRegister(2000)

// Calculate and send command
if status == READY {
target := calculateTarget(soe)
client.WriteRegister(2008, target)
}

Acuvim II Meters​

Overview​

High-accuracy power meters for monitoring site electrical parameters.

Measurements​

  • Voltage (L-L, L-N)
  • Current (per phase)
  • Power (active, reactive, apparent)
  • Energy (import/export)
  • Power factor
  • Frequency

Modbus Configuration​

meter:
type: acuvim2
modbus:
address: 1
baud: 9600
parity: none
data_bits: 8
stop_bits: 1

Register Map​

ParameterStart AddressData TypeScale
Voltage L1-N0x0000Float321
Current L10x0010Float321
Power Total0x0040Float321000
Energy Import0x0100Float321

Communication Protocol​

ModbusTCP Frame​

Transaction ID: 2 bytes
Protocol ID: 2 bytes (0x0000)
Length: 2 bytes
Unit ID: 1 byte
Function Code: 1 byte
Data: Variable

Read Holding Registers (0x03)​

// Read 10 registers starting at 2000
request := []byte{
0x00, 0x01, // Transaction ID
0x00, 0x00, // Protocol ID
0x00, 0x06, // Length
0x01, // Unit ID
0x03, // Function Code
0x07, 0xD0, // Start Address (2000)
0x00, 0x0A, // Quantity (10)
}

Write Single Register (0x06)​

// Write value to register 2008
request := []byte{
0x00, 0x01, // Transaction ID
0x00, 0x00, // Protocol ID
0x00, 0x06, // Length
0x01, // Unit ID
0x06, // Function Code
0x07, 0xD8, // Register Address (2008)
0x00, 0x64, // Value (100)
}

Error Handling​

Common Modbus Exceptions​

CodeNameDescription
0x01Illegal FunctionFunction code not supported
0x02Illegal AddressRegister address invalid
0x03Illegal ValueValue outside valid range
0x04Device FailureDevice unable to process

Retry Logic​

func readWithRetry(addr uint16, retries int) (uint16, error) {
for i := 0; i < retries; i++ {
val, err := client.ReadRegister(addr)
if err == nil {
return val, nil
}
time.Sleep(time.Second * time.Duration(i+1))
}
return 0, fmt.Errorf("max retries exceeded")
}

Configuration Examples​

BESS Configuration​

devices:
bess:
- id: "uuid-here"
name: "Site-BESS-01"
type: "powerpack"
modbus:
host: "192.168.1.100"
port: 502
address: 1
timeout: 5s
retry_count: 3

Meter Configuration​

devices:
meters:
- id: "uuid-here"
name: "Grid-Meter"
type: "acuvim2"
modbus:
host: "192.168.1.101"
port: 502
address: 2
timeout: 5s

Testing Tools​

modpoll​

# Read BESS SOE
modpoll -m tcp -a 1 -r 2026 -c 1 192.168.1.100

# Write target power
modpoll -m tcp -a 1 -r 2008 -c 1 192.168.1.100 50

mbscan​

# Scan for devices
mbscan -p 502 192.168.1.0/24